 "documento": null,
 "pagina": 94,
 "etiqueta_impresa": "94",
 "ancho": 595.2,
 "alto": 842.0,
 "bloques": [
  {
   "i": 0,
   "bbox": [
    244.1,
    36.2,
    367.7,
    45.1
   ],
   "tipo": "texto",
   "texto": "Documento Básico HS Salubridad",
   "tamano": 8.0,
   "negrita": true
  },
  {
   "i": 1,
   "bbox": [
    257.6,
    45.4,
    354.1,
    54.3
   ],
   "tipo": "texto",
   "texto": "HS 4 Suministro de agua",
   "tamano": 8.0,
   "negrita": true
  },
  {
   "i": 2,
   "bbox": [
    70.9,
    795.4,
    311.6,
    805.7
   ],
   "tipo": "texto",
   "texto": "94",
   "tamano": 8.0,
   "negrita": false
  },
  {
   "i": 3,
   "bbox": [
    79.3,
    78.2,
    281.5,
    89.4
   ],
   "tipo": "texto",
   "texto": "4.5.2.3\nCálculo del depósito de presión",
   "tamano": 10.0,
   "negrita": true
  },
  {
   "i": 4,
   "bbox": [
    70.9,
    94.6,
    541.5,
    157.8
   ],
   "tipo": "texto",
   "texto": "1\nPara la presión máxima se adoptará un valor que limite el número de arranques y paradas del grupo\nde forma que se prolongue lo más posible la vida útil del mismo. Este valor estará comprendido en-\ntre 2 y 3 bar por encima del valor de la presión mínima.\n2\nEl cálculo de su volumen se hará con la fórmula siguiente:",
   "tamano": 10.0,
   "negrita": false
  },
  {
   "i": 5,
   "bbox": [
    94.9,
    158.1,
    541.5,
    250.2
   ],
   "tipo": "texto",
   "texto": "Vn  =  Pb x Va / Pa\n(4.2)\nsiendo\nVn\nes el volumen útil del depósito de membrana;\nPb\nes la presión absoluta mínima;\nVa\nes el volumen mínimo de agua;\nPa\nes la presión absoluta máxima.",
   "tamano": 10.0,
   "negrita": false
  },
  {
   "i": 6,
   "bbox": [
    70.9,
    260.6,
    358.2,
    271.8
   ],
   "tipo": "texto",
   "texto": "4.5.3  Cálculo del diámetro nominal del reductor de presión",
   "tamano": 10.0,
   "negrita": true
  },
  {
   "i": 7,
   "bbox": [
    70.9,
    277.1,
    541.4,
    299.7
   ],
   "tipo": "texto",
   "texto": "1\nEl diámetro nominal se establecerá aplicando los valores especificados en la tabla 4.5 en función\ndel caudal máximo simultáneo:",
   "tamano": 10.0,
   "negrita": false
  },
  {
   "i": 8,
   "bbox": [
    131.0,
    303.0,
    481.1,
    322.2
   ],
   "tipo": "texto",
   "texto": "Tabla 4.5 Valores del diámetro nominal en función del caudal máximo simultáneo",
   "tamano": 9.0,
   "negrita": true
  },
  {
   "i": 9,
   "bbox": [
    134.9,
    323.1,
    448.6,
    338.1
   ],
   "tipo": "texto",
   "texto": "Diámetro nominal\nCaudal máximo simultáneo",
   "tamano": 8.0,
   "negrita": true
  },
  {
   "i": 10,
   "bbox": [
    304.9,
    335.3,
    316.9,
    344.2
   ],
   "tipo": "texto",
   "texto": "dm",
   "tamano": 8.0,
   "negrita": true
  },
  {
   "i": 11,
   "bbox": [
    316.9,
    334.0,
    464.1,
    344.2
   ],
   "tipo": "texto",
   "texto": "3/s\nm",
   "tamano": 8.0,
   "negrita": true
  },
  {
   "i": 12,
   "bbox": [
    464.1,
    334.0,
    476.2,
    344.2
   ],
   "tipo": "texto",
   "texto": "3/h",
   "tamano": 8.0,
   "negrita": true
  },
  {
   "i": 13,
   "bbox": [
    164.2,
    348.0,
    473.3,
    356.9
   ],
   "tipo": "texto",
   "texto": "15\n0,5\n1,8",
   "tamano": 8.0,
   "negrita": false
  },
  {
   "i": 14,
   "bbox": [
    164.2,
    360.2,
    473.3,
    369.1
   ],
   "tipo": "texto",
   "texto": "20\n0,8\n2,9",
   "tamano": 8.0,
   "negrita": false
  },
  {
   "i": 15,
   "bbox": [
    164.2,
    372.4,
    473.3,
    381.3
   ],
   "tipo": "texto",
   "texto": "25\n1,3\n4,7",
   "tamano": 8.0,
   "negrita": false
  },
  {
   "i": 16,
   "bbox": [
    164.2,
    384.6,
    473.3,
    393.5
   ],
   "tipo": "texto",
   "texto": "32\n2,0\n7,2",
   "tamano": 8.0,
   "negrita": false
  },
  {
   "i": 17,
   "bbox": [
    164.2,
    396.8,
    473.3,
    405.7
   ],
   "tipo": "texto",
   "texto": "40\n2,3\n8,3",
   "tamano": 8.0,
   "negrita": false
  },
  {
   "i": 18,
   "bbox": [
    164.2,
    409.0,
    475.5,
    417.9
   ],
   "tipo": "texto",
   "texto": "50\n3,6\n13,0",
   "tamano": 8.0,
   "negrita": false
  },
  {
   "i": 19,
   "bbox": [
    164.2,
    421.2,
    475.5,
    430.1
   ],
   "tipo": "texto",
   "texto": "65\n6,5\n23,0",
   "tamano": 8.0,
   "negrita": false
  },
  {
   "i": 20,
   "bbox": [
    164.2,
    433.4,
    475.5,
    442.3
   ],
   "tipo": "texto",
   "texto": "80\n9,0\n32,0",
   "tamano": 8.0,
   "negrita": false
  },
  {
   "i": 21,
   "bbox": [
    162.0,
    445.6,
    475.5,
    454.5
   ],
   "tipo": "texto",
   "texto": "100\n12,5\n45,0",
   "tamano": 8.0,
   "negrita": false
  },
  {
   "i": 22,
   "bbox": [
    162.0,
    457.8,
    475.5,
    466.7
   ],
   "tipo": "texto",
   "texto": "125\n17,5\n63,0",
   "tamano": 8.0,
   "negrita": false
  },
  {
   "i": 23,
   "bbox": [
    162.0,
    470.0,
    475.5,
    478.9
   ],
   "tipo": "texto",
   "texto": "150\n25,0\n90,0",
   "tamano": 8.0,
   "negrita": false
  },
  {
   "i": 24,
   "bbox": [
    162.0,
    482.2,
    477.7,
    491.1
   ],
   "tipo": "texto",
   "texto": "200\n40,0\n144,0",
   "tamano": 8.0,
   "negrita": false
  },
  {
   "i": 25,
   "bbox": [
    70.9,
    494.4,
    477.7,
    529.8
   ],
   "tipo": "texto",
   "texto": "250\n75,0\n270,0\n2\nNunca se calcularán en función del diámetro nominal de las tuberías.",
   "tamano": 10.0,
   "negrita": false
  },
  {
   "i": 26,
   "bbox": [
    70.9,
    540.2,
    409.9,
    551.4
   ],
   "tipo": "texto",
   "texto": "4.5.4 Dimensionado de los sistemas y equipos de tratamiento de agua",
   "tamano": 10.0,
   "negrita": true
  },
  {
   "i": 27,
   "bbox": [
    79.3,
    561.7,
    389.9,
    572.9
   ],
   "tipo": "texto",
   "texto": "4.5.4.1  Determinación del tamaño de los aparatos dosificadores",
   "tamano": 10.0,
   "negrita": true
  },
  {
   "i": 28,
   "bbox": [
    70.9,
    578.1,
    541.4,
    675.8
   ],
   "tipo": "texto",
   "texto": "1\nEl tamaño apropiado del aparato se tomará en función del caudal punta en la instalación, así como\ndel consumo mensual medio de agua previsto, o en su defecto se tomará como base un consumo\nde agua previsible de 60 m3 en 6 meses, si se ha de tratar tanto el agua fría como el ACS, y de 30\nm3 en 6 meses si sólo ha de ser tratada el agua destinada a la elaboración de ACS.\n2\nEl límite de trabajo superior del aparato dosificador, en m3/h, debe corresponder como mínimo al\ncaudal máximo simultáneo o caudal punta de la instalación.\n3\nEl volumen de dosificación por carga, en m3, no debe sobrepasar el consumo de agua previsto en 6\nmeses.",
   "tamano": 10.0,
   "negrita": false
  },
  {
   "i": 29,
   "bbox": [
    79.3,
    686.2,
    422.6,
    697.3
   ],
   "tipo": "texto",
   "texto": "4.5.4.2\nDeterminación del tamaño de los equipos de descalcificación",
   "tamano": 10.0,
   "negrita": true
  },
  {
   "i": 30,
   "bbox": [
    70.9,
    702.6,
    361.4,
    713.8
   ],
   "tipo": "texto",
   "texto": "1\nSe tomará como caudal mínimo 80 litros por persona y día.",
   "tamano": 10.0,
   "negrita": false
  }
 ],
 "error_tablas": null
}